UPS Commercial
B8000FXS

The B8000FXS UPS solution offers parallel options in both redundancy and capacity modes, providing the possibility for both extra system resilience and increased capacity. The parallel control circuitry associated with these units is fully digital and acts on both active and reactive power on each of the three output phases. This allows accurate load current sharing among the UPS units even during transient conditions. Parallel control is distributed between all units and communication is achieved through the use of a CAN BUS connection loop. This has the effect of producing a highly reliable system with “no single points of failure”. Intelligent design of the system connections allow for easy installation and easy future upgrades, this allows for upgrading the field without difficulty. In the modular arrangement, units can be added or removed “hot” without load disturbances or the need to switch to bypass. Smart Parallel functions facilitate the automatic switching off of units where the total power requirements of the load is provided by fewer than the total number of UPS units attached. . This is commonly known as ‘load based shutdown’ and maximises the efficiency of the complete system by keeping the load on each module at an optimum level. Two independent paralleled systems can be synchronized (Sync Control) in order to feed downstream STS’ for seamless transfers.
| MODEL |
B8031FXS
|
B8033FXS
|
||||||
| Rating |
10 kVA
|
15 kVA
|
20 kVA
|
10 kVA
|
15 kVA
|
20 kVA
|
30 kVA
|
40 kVA
|
| Capacity (kVA) |
10
|
15
|
20
|
10
|
15
|
20
|
30
|
40
|
| Dimensions WxHxD (mm) |
450x1200x640
|
|||||||
| Weight (kg) w/o battery |
100
|
110
|
110
|
100
|
110
|
110
|
140
|
140
|
| Weight (kg) with battery |
250
|
260
|
260
|
250
|
260
|
260
|
||
| Input/output connection |
Hardwired (dual input)
|
Hardwired (optional dual input)
|
||||||
| Battery |
Internal or external, 360-372 cells
|
External, 360-372 cells
|
||||||
| INPUT | ||||||||
| Nominal voltage |
220/380, 230/400, 240/415 Vac three phase
|
|||||||
| Voltage range |
-20%, +15% from nominal
|
|||||||
| Frequency |
50/60 Hz (45-65 Hz)
|
|||||||
| Power factor |
0,99
|
|||||||
| Current distortion (THDi) |
<3%
|
|||||||
| OUTPUT | ||||||||
| Nominal voltage |
220, 230, 240 Vac single phase
|
220/380, 230/400, 240/415 Vac three phase
|
||||||
| Frequency |
50/60 Hz
|
|||||||
| Voltage regulation |
±1% static; ± 5% dynamic 100% load change, <10 ms recovery time
|
|||||||
| PF acceptable without de-rating |
Lagging to leading 0,9
|
|||||||
| Overload capacity |
101-125% for 10 mins (on-line), 126-150% for 30 secs (on-line),
|
|||||||
|
1000% for 1 cycle (bypass)
|
||||||||
| Efficiency (SOL) |
94%-98%
|
|||||||
| Efficiency (Eco-mode) |
>98%
|
|||||||
| OPTIONS |
Parallel capacity/redundancy, sync control, isolation transformer, external bypass, external battery cabinets, battery switch box, battery thermal probe, transformers/ autotransformers for voltage adaption
|
|||||||
| USER INTERFACE | ||||||||
| Front panel |
Graphical LCD display, mimic with LED’s and keyboard
|
|||||||
| Standard communication |
RS232 serial, USB, (Remote Emergency Power Off input, Battery Switch status monitoring,
|
|||||||
| ports |
External Manual Bypass status monitoring, Diesel Mode)
|
|||||||
| Optional |
Web/SNMP, ModBus, relay, modem cards; remote panel; monitoring, managing and shutdown software
|
|||||||
| ENVIRONMENTAL | ||||||||
| Operating temperature |
0°C - +40°C
|
|||||||
| Storage temperature |
-10°C - +70°C
|
|||||||
| Altitude |
<1000 m
|
|||||||
| Audible noise at 1 meter (dBA) |
<52
|
|||||||
| STANDARDS AND CERTIFICATION | ||||||||
| Marking |
CE, GOST, ECA, ETL
|
|||||||
| Safety |
IEC EN 62040 -1
|
|||||||
| EMC |
IEC EN 62040 -2
|
|||||||
| Test and Performance |
IEC EN 62040 -3
|
|||||||
| Quality and Environment |
ISO 9001: 2008, ISO 14001: 2004
|
|||||||
The B8000FXS has a new SOL (Smart On-Line) function which enables a total operating efficiency of between 94% and 98%. This mode referred to as ‘Intelligent ECO mode’ significantly reduces the utility costs associated with operating a device of this type. Moreover, this increase in efficiency results in the production of less waste heat, minimising cooling/air-conditioning costs. This represents a double saving to the energy conscious user. Manageability and compact design further decrease the cost of ownership in terms of installation and maintenance. The SOL function uses continual monitoring techniques to review the input characteristics of the supply. This means that if the supply line drops or fluctuates outside of acceptable conditions the UPS uses the internal inverter to support the load. This is achieved through a fast, fully static transition